Custom and pre-engineered packaged fire pump systems that are factory assembled and tested, leaving only pipe connections, power connections and structural base grouting to be completed on site.
Custom and pre-engineered packaged fire pump systems that are factory assembled and tested, leaving only pipe connections, power connections and structural base grouting to be completed on site. All fire pump packages built to NFPA 20 & NEC standards with UL listed/FM approved components.
Fire Pump Packages Standard Equipment
UL listed/FM approved Aurora fire pump
UL listed/FM approved fire pump controller
Aurora jockey pump
UL listed jockey pump controller
Pressure sensing lines complete per NFPA 20
UL Listed / FM approved OS&Y gate valves, butterfly valves and check valves
Suction and discharge pressure gauges
Automatic casing air release valve
Casing pressure relief valve (electric packages)
Hose header with valves, caps & chains
Suction and discharge piping per NFPA 20
All electrical components pre-wired at factory
Complete system hydrostatically tested
Diesel Driven Fire Pump Packages also include:
Dual batteries with racks and charger
UL listed fuel tank sized per NFPA 20
Residential grade muffler
Flexible exhaust connector
Engine cooling loop
Options Available:
Witnessed and non-witnessed complete system performance test
Test line outlet to connect to remote tank with FM approved flow meter, isolation valves and air release valve
Test loop back to suction with FM approved flow meter, isolation valves and air release valve
Bypass loop with check valve, isolation valves & air release valve
Main system pressure relief valve with enclosed waste cone
Relief valve for jockey pump line
Double wall fuel tank with low fuel and leak detection alarms
Backflow preventor
Critical grade muffler
Packaged system drains piped to edge of skid
Complete fire pump house
Fire Pumps
Vertical Inline Single Stage Fire Pump
Model: 383
Offers space-saving efficiency, and flexibility for smaller spaces.
Flows: 50 to 1,500 GPM (11.3 to 340 m3/hr)
Pressures: 40 to 159 PSI (2.7 to 11 bar)
UL Listed/FM Approved/NFPA-20 Design
Space Saving Vertical Design
Easy Maintenance without Disturbing Surrounding Piping
Bronze-Fitted Pump Construction
End Suction Fire Pump
Model: 384
Flows: 50 to 1500 GPM (11.3 to 340 m3/hr)
Pressures: 40 to 225 PSI (2.7 to 15.5 bar)
UL Listed, FM Approved Performance
Electric and Diesel Speeds
Back Pullout Design for Easy Pump Service without Disconnecting Pipe
Frame-Mounted Design
Small Footprint Ideal for Retrofit
Designed for Installations such as Schools, Office Buildings and Hospitals
Horizontal Split Case Electric Drive Fire Pumps
Models: 481, 485, 491, 492, 495
Flows: 250 to 5,000 GPM (56.8 to 1135 m3/hr)
Pressures: 40 to 435 PSI (2.7 to 30 bar)
UL Listed/FM Approved/NFPA-20 Design
F or Commercial, Industrial and Marine Use
Diesel and Electric Driven Available
Ease of Maintenance
Vertical Split Case Electric Drive Fire Pump
Model: 483
Flows: 250 to 2,500 GPM (56.8 to 568 m3/hr)
Pressures: 40 to 200 PSI (2.7 to 13.8 bar)
UL Listed/FM Approved/NFPA-20 Design
F or Commercial, Industrial and Marine Use
Electric Driven Available
Lower Initial Cost
Ease of Maintenance
Horizontal Split Case Diesel Drive Fire Pumps
Models: 481, 485, 491, 492, 495
Flows: 250 to 5,000 GPM (56.8 to 1,135 m3/hr)
Pressures: 40 to 435 PSI (2.8 to 30 bar)
UL Listed/FM Approved/NFPA-20 Design
F or Commercial, Industrial and Marine Use
Diesel and Electric Driven Available
Lower Initial Cost
Quicker Delivery with Red Hot Quick Ship Program
Ease of Maintenance
Fire Pump Vertical Turbine
Flows: 250 to 4,500 GPM (56.8 to 1,022 m3/hr)
Pressures: 50 to 370 PSI (3.4 to 25.5 bar)
UL Listed/FM Approved/NFPA-20 Design
F or Commercial, Industrial and Marine Use
Special Materials for Seawater Applications
Diesel and Electric Driven
Jockey Pumps
Models: PVM & PVMX
Horsepower: 1/2 to 40
Flow Series: 1, 3, 5, 10, 15, 20, 33
Capacities: Up to 210 GPM (47.6 m3/hr)
Pressures: 330 PSI (22.7 bar)
Heads: 800 Feet (244 m)
Temperatures: 250°F (121°C)
Cartridge Mechanical Seal – can be replaced easily without dismantling the pump
Available in Cast Iron or 316 Stainless Steel Materials
Standard TEFC Motor
Retrofits easily in existing and new installations
Features
A. Aurora Fire Pump
B. Motor
C. Control Panel (Fire Pump)
D. Test Loop
E. Multi-stage Jockey Pump
F. Control Panel (Jockey Pump)
G. OS & Y Gate Valve
H. Swing Check Valve
I. Flow Meter
J. Suction Pressure Gauge
K. Discharge Pressure Gauge
L. Coupling (Guard Not Shown)
M. Relief Valve (Jockey Pump Line)
N. Air Release Valve (Pump Casing)
O. Relief Valve (Fire Pump)
P. Air Release (Test Loop)
Q. Check Valve (Jockey Pump Line)
R. OS & Y Gate Valve (Jockey Pump Suction)
S. OS & Y Gate Valve (Jockey Pump Discharge)
T. Butterfly Valve
U. Concentric Increaser
V. Eccentric Reducer
W. Butterfly Valve (Test Loop)
Aurora Pump offers vertical turbine fire pump systems for static suction conditions. Vertical turbine systems come complete with pump, driver, controller, flow-measuring device, relief valve with waste cone, check valves, and pressure sensing line.
Systems
Pentair Aurora packaged fire pump systems are fully-integrated and custom-engineered, designed and built to meet and exceed the requirements for each unique job specification. They are built to the stringent standards of NFPA 20, UL,FM, and other regulatory bodies, and ship fully tested and certified to the highest quality standards. Packaged fire pump systems provide single source system responsibility for maximum reliability and up-time.
Packaged Fire Pump systems include the pump, driver, controller, jockey pump and jockey pump controller, and other required components mounted on a common base. Whether simplex, duplex, or triplex configuration, electric motor or diesel engine driven, the systems are pre-piped and pre-wired for ease and speed of installation. Every detail is integrated in a fully coordinated system to ensure that the heart of the system performs perfectly, now and in the future.
Pentair’s Packaged Fire Pump systems are available with full protective enclosures suitable for any climate or site condition. To address applications in harsh environments or with sea or brackish water, pumps and other components are available in advanced metallurgies including 316 Stainless Steel, Duplex and Super Duplex Stainless Steel, and Nickel Aluminum Bronze. System accessories include a full range of jockey pumps, UL/FM valves and other UL/FM accessories.
Custom and pre-engineered packaged fire pump systems are factory assembled and tested, leaving only pipe connections, power connections and structural base grouting to be completed on site. All fire pump packages built to NFPA 20 & NEC standards with UL listed/FM approved components.
UL Listed/FM Approved Aurora® Fire Pump
UL Listed/FM Approved Fire Pump Controller
ETL Listed
Aurora Jockey Pump
UL Listed Jockey Pump Controller
Pressure Sensing Lines Complete per NFPA 20
Listed OS & Y Gate & Butterfly Valves with Tamper Switches
Suction and Discharge Pressure Gauges
Automatic Casing Air Release Valve
Casing Pressure Relief Valve (Electric Packages)
Hose Header with Valves, Caps & Chains
Suction and Discharge Piping per NFPA 20
Removable Lifting Lugs
Compact Fire Pump Systems
Flows to 750 GPM (170.3 m3/hr)
Pressures to 160 PSI (11.0 bar)
Ideal for Smaller Areas – Fits through a 36″ Doorway
Multiple Starting Methods Available for the Fire Pump with Optional Automatic Transfer Switch